Air Changes per Hour
Enter airflow in m³/h and the room’s volume. The result is a nominal flow-to-volume ratio, not a ventilation compliance or infection-risk assessment.
Let’s calculate.
Usage estimateCalculate nominal room air changes from a known flow.
Formula and worked example
ACH = air volume flow per hour / room volume
Reference example
300 m³/h through a 100 m³ room gives 3 changes per hour.
When this calculation applies
Flow remains m³/h; convert L/s or m³/s before entry. This is nominal ACH, not the fraction of air replaced in one hour under mixing, an infection-risk estimate or proof of ventilation compliance.
Background reference: cdc.gov. References explain the method or units; they do not certify this calculator.
Source scope: CDC defines air changes per hour as airflow divided by room volume. This nominal ratio alone does not establish air cleanliness, outdoor-air provision or compliance.
For the derivation, input conventions and numerical limits, open .
How to use this result
An airflow of 80 L/s equals 80 × 3.6 = 288 m³/h. For a 96 m³ room this gives 3 h⁻¹. Enter 288, not 80, in the fixed m³/h airflow field.
Does 3 air changes mean all the old air is gone after 20 minutes?
No. The number describes a flow equivalent to three room volumes per hour. Mixing, short-circuiting, dead zones and the contaminant source affect actual replacement or removal. The ratio alone is not a purge-time model.
Should I enter total supply air or outdoor air?
That depends on the quantity you intend to describe. Recirculated supply flow and outdoor-air flow are not interchangeable for ventilation claims. Label the airflow basis and use measurements relevant to the actual system.
Does the result show that the room is safe or compliant?
No. Occupancy, pollutant sources, distribution, filtration and applicable requirements need separate assessment. The calculator does not recommend a target or infer clean-air delivery from a fan’s nominal rating.